CPX-FB33 Bus node 548755
Data sheet
|
Feature |
value |
|
Protocol |
PROFINET IRT PROFINET RT |
|
Dimensions(W x L x H) |
(incl.interlinking block) 50x107x50mm |
|
Product weight |
185g |
|
Ambient temperature |
-5℃...50℃ |
|
Storage temperature |
-20°C.….70℃ |
|
Degree of protection |
IP65 IP67 |
|
Corrosion resistance class CRC |
0-No corrosion stress |
|
LABS(PWIS)conformity |
VDMA24364-B2-L |
|
Approval |
RCM trademark |
|
Note on materials |
RoHS - compliant |
|
Material housing |
Die-cast aluminium |
|
LED display,product-specific |
M:Modify,parameterisation PL:Load supply PS:Electronics supply,sensor supply SF:System fault |
|
LED display,bus-specific |
M/P:maintenance/PROFlenergy NF:Network fault TP1:Network active port 1 TP2:Network active port 2 |
|
Device-specific diagnostics |
Channel-oriented and module-oriented diagnostics Undervoltage of modules Diagnostic memory |
|
Operator controls |
DIL switch |
|
Field bus interface |
2x socket,M12x1,4-pin,D-coded |
|
Max.address volume,inputs |
64 Byte |
|
Max.address volume,outputs |
64 Byte |
|
Parameterisation |
Diagnostic behaviour Fail-safe response Forcing of channels Signal setup System parameter |
|
Baud rate |
100 Mbit/s |
|
Configuration support |
GSDML file |
|
Feature |
Value |
|
Additional functions |
Acyclic data access via fieldbus Asynchronous data access via Ethernet Fast start-up(FSU) I&M Channel-oriented diagnostics via fieldbus LLDP MQTT MRP MRPD PROFlenergy PROFlsafe S2 system redundancy Start-up parameterisation in plain text via fieldbus System status can be mapped using process data Additional diagnostic interface for operator units |
|
Operational voltage range DC |
18V...30V |
|
Nominal operating voltage DC |
24V |
|
Intern power consumption nominal operating voltage |
Typ.70 mA |
About this document
Applicable documents
ALL available documents for the product→ www.festo.com/sp.
|
Document |
Contents |
|
CPX system description CPX ·SYS… |
Detailed information on the CPX terminal |
|
Brief instructions for bus node |
Essential information on the product |
|
Operating instructions for bus node |
Detailed information on the product |
Tab.1:Applicable documents
Safety
Safety Instructions
Only use the product in original status without unauthorised modifications.
Only use the product if it is in perfect technical condition.
Observe labelling on the product.
Store the product in a cool,dry,UV-protected and corrosion-protected environ- ment.Ensure that storage times are kept to a minimum.
Before working on the product,switch off the power supply and secure it against being switched on again.
This product can generate high frequency malfunctions,which may make it nec- essary to implement interference suppression measures in residential areas.Comply with the handling specifications for electrostatically sensitive devices.
Intended use
The bus node is intended for operation as a station(1O Device)in the Industrial Ethernet system PROFINET IO.
When the additional Message Queuing Telemetry Transport(MQTT)function is activated,the bus node can be used as a gateway between Industrial Ethernet networks and an on-premise MQTT broker.
The product may only be used in combination with the CPX Terminal in an indus- trial environment.
Product variants
The following software and hardware revisions are a prerequisite for using the functions:
|
Function
|
Bus bus node revision number |
|
|
Software |
Hardware |
|
|
Priority start-up(Fast Start-up) |
from Rev 12 |
from Rev 11 |
|
ldentification &Maintenance (8M) |
from Rev 14 |
from Rev 1 |
|
PROFlenergy |
from Rev 20 |
from Rev 1 |
|
Media Redundancy Protocol (MRP) |
from Rev 20 |
from Rev 1 |
|
Media Redundancy for Planned Duplication(MRPD) |
from Rev 50 |
from Rev 45 |
|
S2 system redundancy |
from Rev 50 |
from Rev 45 |
|
Isochronous real time (IRT) |
from Rev 21 |
from Rev 1 |
|
Message Queuing Telemetry Transport(MQTT) |
from Rev53 |
from Rev 45 |
Tab.2:Required revision numbers for using the functions
The bus nodes CPX(-M)-FB33/34/35 do not support MQTT.
The revision numbers of the hardware and software for the bus node can be checked with the control software,the Festo Maintenance Tool(FMT)or the Festo Field Device Tool(FFT).
LED displays
|
LED |
Network status LEDs |
LED |
CPX-specific LEDs |
||
|
○ |
NF |
Network Failure,red |
○ |
PS |
Power System, green |
|
○ |
M/P |
Maintenance/PROFlenergy, green or yellow |
○ |
PL |
Power Load,green |
|
○ |
TP1 |
Link/Traffic 1,green |
○ |
SF |
System Failure,red |
|
○ |
TP2 |
Link/Traffic 2,green |
○ |
M |
Modify,yellow |
Tab.3:LEDs on the bus node
Reserved DlL switches are blocked for future functions and must not be used.
The setting of the DlL switches for operating mode and diagnostics mode mustmatch the settings in the open-loop control.
Memory card
The bus nodes CPX-(M)-FB43/44/45 do not support memory cards.
The memory card serves as a carrier for configuration data, such as the fieldbudevice name. This makes it easy to replace a bus node. Detailed information oruse.Bus node operating instructions.
NOTICE
Malfunction or Damage to the Memory Card.
Inserting or removing the memory card while the power supply is switched on can result in malfunctions of or damage to the memory card.
·Disconnect the power supply before you insert or remove the memory card.
The various bus node revisions are only compatible with the corresponding memory card:
|
Memory card |
Bus bus node revision number |
|
CPX-SK |
from Rev 07 |
|
CPX-SK-2 |
from Rev 12 |
|
CPX-SK-3 |
from Rev 30 |
Tab.6:Compatibility of the memory cards depending on the bus node revision
Overview of connections and plug
|
Bus node |
Connection technology |
Network connectors |
|
CPX-FB33/43 |
2×M12,D-coded,female,4-pin,in accordance with IEC61076-2 |
NECU-MS-D12G4-C2-ET |
|
CPX-M-FB34/44 |
2×RJ45,push-pull,Cu,AIDA, in accordance with IEC60603, IEC61076-3 |
FBS-RJ45-PP-GS |
|
CPX-M-FB35/45 |
2×SCRJ,push-pull,650nm,AIDA,in accordance with IEC61754-24 |
FBS-SCRJ-PP-GS |
Tab.10:Connection technology and network connectors
In the following table,the cable lengths were used in accordance with the specifi-cations for PROFlNET networks.
|
Network connectors |
Cable specification |
|
NECU-MS-D12G4-C2-ET |
Ethernetcable,shielded,Cat 5/5e,6...8mm,0.14...0.75mm²; max.100 m PROFINET end-to-end link:22 AWG |
|
FBS-RJ45-PPGS |
Etherne cable,shielded,Cat 5/Cat 5e,5...8mm, 0.13….0.36 mm²△ca.26.…22 AWG; max.100m PROFINET end-to-end link:22 AWG |
|
FBS-SCRJ-PP-GS |
POF fibre-optic cable,980/1000 μm,6.5...9.5mm; max.50m PROFINET end-to-end link;s12.5 dB |
Tab.11:Cable specification for network connectors
Service interface
An operator unit such as CPX-MMI-1 can be connected to the service interface.
Alternatively,the service interface can be connected to a PC via the USB adapter NEFC-M12G5-0.3-U1G5 so that the"Festo Maintenance Tool"software(FMT)can be used.