CPX-FB43 8110369
Data sheet
|
Feature |
value |
|
Protocol |
PROFINET IRT PROFINET RT |
|
Dimensions(W x L x H) |
(incl.interlinking block) 50x107x50mm |
|
Product weight |
185g |
|
Ambient temperature |
-5℃...50℃ |
|
Storage temperature |
-20°C.….70℃ |
|
Degree of protection |
IP65 IP67 |
|
Corrosion resistance class CRC |
0-No corrosion stress |
|
LABS(PWIS)conformity |
VDMA24364-B2-L |
|
Approval |
RCM trademark |
|
Note on materials |
RoHS - compliant |
|
Material housing |
Die-cast aluminium |
|
LED display,product-specific |
M:Modify,parameterisation PL:Load supply PS:Electronics supply,sensor supply SF:System fault |
|
LED display,bus-specific |
M/P:maintenance/PROFlenergy NF:Network fault TP1:Network active port 1 TP2:Network active port 2 |
|
Device-specific diagnostics |
Channel-oriented and module-oriented diagnostics Undervoltage of modules Diagnostic memory |
|
Operator controls |
DIL switch |
|
Field bus interface |
2x socket,M12x1,4-pin,D-coded |
|
Max.address volume,inputs |
64 Byte |
|
Max.address volume,outputs |
64 Byte |
|
Parameterisation |
Diagnostic behaviour Fail-safe response Forcing of channels Signal setup System parameter |
|
Baud rate |
100 Mbit/s |
|
Configuration support |
GSDML file |
|
Feature |
Value |
|
Additional functions |
Acyclic data access via fieldbus Asynchronous data access via Ethernet Fast start-up(FSU) I&M Channel-oriented diagnostics via fieldbus LLDP MQTT MRP MRPD PROFlenergy PROFlsafe S2 system redundancy Start-up parameterisation in plain text via fieldbus System status can be mapped using process data Additional diagnostic interface for operator units |
|
Operational voltage range DC |
18V...30V |
|
Nominal operating voltage DC |
24V |
|
Intern power consumption nominal operating voltage |
Typ.70 mA |
Safety Instructions
Product variants
|
Function
|
Bus bus node revision number |
|
|
Software |
Hardware |
|
|
Priority start-up(Fast Start-up) |
from Rev 12 |
from Rev 11 |
|
ldentification &Maintenance (8M) |
from Rev 14 |
from Rev 1 |
|
PROFlenergy |
from Rev 20 |
from Rev 1 |
|
Media Redundancy Protocol (MRP) |
from Rev 20 |
from Rev 1 |
|
Media Redundancy for Planned Duplication(MRPD) |
from Rev 50 |
from Rev 45 |
|
S2 system redundancy |
from Rev 50 |
from Rev 45 |
|
Isochronous real time (IRT) |
from Rev 21 |
from Rev 1 |
|
Message Queuing Telemetry Transport(MQTT) |
from Rev53 |
from Rev 45 |
LED displays
|
LED |
Network status LEDs |
LED |
CPX-specific LEDs |
||
|
○ |
NF |
Network Failure,red |
○ |
PS |
Power System, green |
|
○ |
M/P |
Maintenance/PROFlenergy, green or yellow |
○ |
PL |
Power Load,green |
|
○ |
TP1 |
Link/Traffic 1,green |
○ |
SF |
System Failure,red |
|
○ |
TP2 |
Link/Traffic 2,green |
○ |
M |
Modify,yellow |
Memory card
|
Memory card |
Bus bus node revision number |
|
CPX-SK |
from Rev 07 |
|
CPX-SK-2 |
from Rev 12 |
|
CPX-SK-3 |
from Rev 30 |
|
Bus node |
Connection technology |
Network connectors |
|
CPX-FB33/43 |
2×M12,D-coded,female,4-pin,in accordance with IEC61076-2 |
NECU-MS-D12G4-C2-ET |
|
CPX-M-FB34/44 |
2×RJ45,push-pull,Cu,AIDA, in accordance with IEC60603, IEC61076-3 |
FBS-RJ45-PP-GS |
|
CPX-M-FB35/45 |
2×SCRJ,push-pull,650nm,AIDA,in accordance with IEC61754-24 |
FBS-SCRJ-PP-GS |
|
Network connectors |
Cable specification |
|
NECU-MS-D12G4-C2-ET |
Ethernetcable,shielded,Cat 5/5e,6...8mm,0.14...0.75mm²; max.100 m PROFINET end-to-end link:22 AWG |
|
FBS-RJ45-PPGS |
Etherne cable,shielded,Cat 5/Cat 5e,5...8mm, 0.13….0.36 mm²△ca.26.…22 AWG; max.100m PROFINET end-to-end link:22 AWG |
|
FBS-SCRJ-PP-GS |
POF fibre-optic cable,980/1000 μm,6.5...9.5mm; max.50m PROFINET end-to-end link;s12.5 dB |
About this document
|
Document |
Contents |
|
CPX system description CPX ·SYS… |
Detailed information on the CPX terminal |
|
Brief instructions for bus node |
Essential information on the product |
|
Operating instructions for bus node |
Detailed information on the product |