CPX-M-16DE-D
Data sheet
|
Feature |
Value |
|
Dimensions(W×L×H) |
(incl.interlinking block and connection technology) 50×107×50mm |
|
Product weight |
46g |
|
Ambient temperature |
-5℃...50℃ |
|
Storage temperature |
-20C...70℃ |
|
Degree of protection |
Dependent on the manifold block |
|
Corrosion resistance class CRC |
1-Low corrosion stress (when installed) |
|
LABS(PWIS)conformity |
VDMA24364-B2-L |
|
Material housing |
PA-reinforced PC |
|
LED display |
1 Group diagnostics 16channel diagnostics/channel status |
|
Diagnosis |
Short circuit/overload per channel |
|
Parameterisation |
Input debounce time Signal extension time Behaviour after short circuit Module monitoring |
|
operational voltage range DC |
18V...30V |
|
Nominal operating voltage DC |
24V |
|
Intern power consumption nominal operating voltage |
Typ.34 mA |
|
Number of inputs |
16 |
|
Characteristic for inputs |
IEC1131-T2 |
|
Switching level |
Signal 0:<=5V Signal 1:>=11V |
|
Switching logic for inputs |
PNP(positive switching) |
|
Input debounce time |
3ms(0.1 ms,10 ms,20 ms,parameterisable) |
|
Max.residual current of inputs per module |
1.8A |
|
lsolation channel-channel |
no |
|
lsolation channel -internal bus |
no |
|
Fuse protection(short circuit) |
Internal electronic fuse per channel pair Additional fuse |