VABA-S6-1-X2
Data sheet
|
Feature |
Value |
|
Valve terminal interface |
Type 44,VTSA |
|
Diagnosis |
Undervoltage of valves |
|
Max.number of valve positions |
16with bistable valves 32 with monostable valves |
|
LED display |
1Group diagnostics Channel status on valves |
|
Parameterisation |
Fail-safe per channel Forcing per channel Idle mode per channel Module monitoring |
|
Fuse protection (short circuit) |
Internal electronic fuse protection per valve output |
|
Operational voltage range DC |
21.6V...26.4V |
|
Intern power consumption nominal operating voltage |
Typ.15mA(power supply for electronics) Typ.50 mA(load voltage supply for valve) |
|
Max.power supply per channel |
0.2 A |
|
Max.total current per module |
4A |
|
Nominal operating voltage DC |
24V |
|
Isolation channel-internal bus |
Yes,when using an additional power supply for the valves |
|
Corrosion resistance class CRC |
0-No corrosion stress |
|
LABS(PWIS)conformity |
VDMA24364-B1/B2-L |
|
Degree of protection |
IP65 NEMA4 |
|
Ambient temperature |
-5℃...50℃ |
|
Product weight |
590g |
|
Electrical control |
Fieldbus |
|
Electrical connection |
Via CPX |
|
Note on materials |
RoHS-compliant |
|
Material cover |
PA |
|
Material housing |
Die-cast aluminium |